SCI

SCI Energy Efficiency

SCI ENERGY SAVING

SAME
PERFORMANCE.
LESS POWER.

SCI chambers match cooling output to the real test load, helping laboratories reduce operating energy by 30% or more—without compromising temperature control.

Internal comparative tests · Real meter readings · Profile-specific review

MEASURED EXAMPLETEST DATA
33%
less energy at −20°C hold
Conventional control21 kWh
SCI adaptive control14 kWh
1 m³ rapid temperature-change chamber · 1 hour

30%+

typical energy-saving target

3

coordinated control layers

24/7

savings accumulate while running

1:1

review against your test profile

WHY IT USES LESS

Stop paying for
energy conflict.

Conventional hot–cold balance control may keep refrigeration at high output, then add heat to hold the setpoint. SCI changes the cooling source itself—so the chamber receives only the energy it needs.

TRADITIONAL CONTROLEnergy conflict
FULL COOLING
WASTE
REHEATING

Excess cooling is cancelled by electric heating just to maintain the target temperature.

SCI ADAPTIVE CONTROLDemand matched
SETPOINT
OUTPUT FOLLOWS LOAD

Cooling capacity tapers with the real load, with little or no reheating during stable holds.

01

Adaptive PID control

Cooling and heating output follow the real test load—without fighting each other at steady state.

02

Variable-frequency cooling

Compressor speed and output are continuously matched to demand, reducing repeated starts and wasted capacity.

03

Electronic flow control

Fast refrigerant regulation keeps control precise across low-temperature and high-load conditions.

REAL CONTROLLER EXPORTS

Two chambers. One direct comparison.

Profile A is the reference competitor chamber. Profile B is the SCI chamber. Both are multi-day controller exports used to compare measured energy consumption at corresponding temperature and humidity hold points.

REFERENCE CHAMBERConventional hot–cold balance
Reference competitor chamber controller export showing the multi-stage test and measured energy
SCI CHAMBERAdaptive cooling control
SCI chamber controller export showing the corresponding multi-stage test and measured energy

HOW TO READ THE TEST

Do not compare individual colors as two brands. Compare the two complete panels.

01

First, identify the two chambers

Panel A is the competitor reference. Panel B is the SCI chamber. The multiple colored traces inside each panel are controller channels—not separate brands.

02

Then, align the same hold point

Compare corresponding temperature or humidity plateaus. Both chambers must reach and hold the required condition before their consumption is judged.

03

Finally, compare measured kWh

The electricity channel records real consumption on the same timeline. At the matched hold points, SCI generally uses fewer kWh—showing that cooling output is reduced when full capacity is unnecessary.

WHAT THE DATA SHOWS

Energy savings increase when the control system no longer has to fight itself.

Selected values below come from the supplied 1 m³, −70°C temperature-humidity chamber comparison. Each temperature point was held for two hours; the combined 85°C / 85% RH point was held for one hour.

ALL 14 SUPPLIED TEST POINTS

Every point is shown—including the neutral 23°C / 30% RH result—to avoid cherry-picking.

−60°C18%energy saved
−40°C64%energy saved
−20°C25%energy saved
0°C38%energy saved
25°C75%energy saved
50°C90%energy saved
85°C90%energy saved
100°C50%energy saved
125°C50%energy saved
150°C50%energy saved
23°C / 30% RH0%energy saved
23°C / 50% RH20%energy saved
23°C / 95% RH25%energy saved
85°C / 85% RH80%energy saved
Test profileSCIConventionalSaving
−40°C hold2 hours5 kWh14 kWh−64%
25°C hold2 hours2 kWh8 kWh−75%
85°C hold2 hours1 kWh10 kWh−90%
85°C / 85% RH1 hour1 kWh5 kWh−80%

“The important number is not installed power. It is the energy actually consumed over your real test cycle.”

Source: SCI internal comparative measurement records for a 1 m³, −70°C temperature-humidity chamber. Results are not a guarantee; actual savings vary by model, test profile, ambient conditions and specimen load.

Power meter used for chamber energy measurement
FIELD EVIDENCE Direct electrical metering during chamber operation

SECOND MEASURED DATASET

Fast-changing tests.
Even larger savings.

A separate 1 m³ rapid temperature-change humidity chamber was measured under low-temperature holds, high temperature, high humidity and a −40°C to 85°C cycle at an average 15°C/min.

ALL-PROFILE AVERAGEMEASURED
64%

average energy saving across the supplied temperature and humidity profiles

Traditional hot–cold balance25.6 kWh avg.
SCI adaptive cooling9.3 kWh avg.
TEST PROFILEENERGY / SAVING
−40°C hold1 hour
15 vs 24 kWh−38%
−20°C hold1 hour
14 vs 21 kWh−33%
85°C hold1 hour
2.5 vs 25 kWh−90%
40°C / 95% RH1 hour
10 vs 22 kWh−55%
−40°C ↔ 85°C15°C/min cycle
13 vs 60 kWh−78%
What this adds to the evidence:

SCI’s advantage is not limited to steady-state operation. It remains visible during high-load temperature cycling, where conventional control consumed 60 kWh versus 13 kWh in the supplied test.

SIX TEMPERATURE HOLD POINTS

Lower power while
holding temperature.

Each point was tested for five hours. Values show average energy used per hour under the same 1 m³ no-load comparison.

SCI AVERAGE2.13 kWh/h

Lowest result at 5 of 6 hold points

IMPORTED COMPARISON2.27 kWh/h

Lower than SCI only at −40°C

DOMESTIC COMPARISON3.86 kWh/h

SCI uses 45% less on average

SCI chamberImported comparisonDomestic comparison
−40°C
3.47 kWh/h
2.40 kWh/h
7.68 kWh/h
−20°C
1.92 kWh/h
1.97 kWh/h
3.41 kWh/h
0°C
1.89 kWh/h
2.00 kWh/h
3.11 kWh/h
25°C
1.85 kWh/h
2.25 kWh/h
3.05 kWh/h
35°C
1.83 kWh/h
2.48 kWh/h
3.10 kWh/h
45°C
1.81 kWh/h
2.53 kWh/h
2.82 kWh/h

Transparent comparison: the imported unit is lower at −40°C, while SCI records the lowest consumption at the other five supplied hold points. Actual project results depend on chamber configuration, load and ambient conditions.

INTERACTIVE LIFECYCLE VALUE MODEL

What Could 30% Lower Energy Use Be Worth Across Your Lab?

Enter the number of chambers and baseline average energy use per chamber, then set actual operating days and peak / standard / off-peak hours.

CONSERVATIVE BASIS · 30%

Tariff presets are editable planning references—not utility quotations. Replace them with your actual invoice rates for a project estimate.

ESTIMATED ANNUAL ELECTRICITY SAVINGMYR 2,988
ENERGY AVOIDED / YEAR10,080 kWh
YEARS TO ONE MACHINE-EQUIVALENT11 years
5-YEAR OPERATING VALUEMYR 14,941
BLENDED ENERGY RATEMYR 0.2965/kWh
One-year progress toward the entered machine value9%

7.0 baseline kWh/h × 30% × 1 chamber(s) × 16.0 h/day × 300 days = 10,080 kWh avoided / year.

Planning estimate only. Actual savings vary by chamber model, temperature profile, specimen load, ambient conditions and local tariff.

SEND US YOUR TEST PROFILE

We’ll compare energy use before you buy.

ENGINEERING CONSULTATION

Turn your requirement into a buildable chamber specification.

Share the essentials. Our application engineers will help define a practical, reliable system.

Application and standards reviewPractical chamber configurationInitial response within 1 business day
SCI INSTRUMENTS CO.LTD
info@scicoolings.com
PROJECT ENQUIRY

Request Engineering Consultation

Tell us the essentials. Our application engineers will help complete the specification.

Quick Chamber Selection
Select your test method, control variables and workspace. SCI will use these inputs to recommend the practical configuration.